![]() Merits: 1) By installing the signal conditioner in the field, you do not have to lead AC output from transformers as far as to control panel of the DCS: there is no special consideration on cables required for AC transmission or their installation. 2) You can get standard 4 to 20 mAdc output from the signal conditioner: with L-Unit PT and CT Transducers models LPNE/LCNE which take their driving power from input loop, you can only have a signal such as 0 to 1 mAdc, the lower range output of which equals zero; thus receiving 0 mA output, you cannot be sure if a leadwire breaks or opens. 3) The signal conditioners installed in the field are more independent from the central DCS than those installed in racks at the control section of the DCS: users can freely design the field system only if current loop supply units are in the DCS. |