The
Math Function Module does not have an indicator, therefore an engineering unit
scale is n ot used. Its input and output signals are limited to 4 20 mA
DC or 1 5 V DC. Computations within the module are carried out using numerical
values of 0 1 or 0 100%. When input and/or output conditions change,
the preset constants in the module must also be changed which can involve somewhat
complicated procedures. That is to say, gains and biases for the computation equation
s hould be re-calculated. In these calculations, the specific engineering unit
scalings should be used for bo th input and output signal ranges.
As
a typical example, Figure 4 shows the calculation procedure for the application
shown in Figure 1. The input and output signal ranges for this example are as
follows:
Flow 1: 0 100 m3/H |
Flow 2: 0 200 m3/H |
Output: 0 300 m3/H |
In this case, all engineering unit scales start at zero which means that bias
need not be considered. Therefore, the following equation is used for the Math
Function Module:
X0 = K1 x X1 + K2 x X2 |
Where, X0 = 0
1, Output Signal |
X1 = 0 1, Input
Signal (Flow 1) |
X2 = 0 1, Input
Signal (Flow 2) |
In
most basic applications, the equation: Output = Flow 1 + Flow 2 is used. However,
in this example the output range becomes 0 2 using this formula, instead
of the 0 1 intended range. Because of this, values for gains K1 and K2 must be determined. The following equations
are used to determine their values:
The actual calculation for the example shown in Figure 4 is:

  |