like to propose you to install the power transducer, model LTWT at each
electric power inlet point. The LTWT take in AC active power and provide
a DC output signal and pulse signal proportionally. And then please put
the pulse output signal into the PC Recorder module, the R1M-P4. The R1M-P4
takes in the pulse signal as totalized counter input.
You
can monitor the totalized pulse record on the PC Recorder software on
your PC via RS-232C. PC recorder software, MSRPAC-2005 is coming along
with the R1M-P4 for free of charge. The R1M-P4 has counter reset function.
Therefore if you need to monitor every 30-minute amount of power, please
set an external timer-controlled relay and apply a contact input to the
R1M-P4 in every 30-minute as counter reset signal.
Demand Monitoring Contract (example in Japan) Amount of power usage in every 30-minute is contracted between Power Company
and Commercial-Scale utility customers. It is called Demand Monitoring
Contract in Japan. If customers amount of power usage goes
over the contracted limitation, penalty charges will be required and/or
next coming amount of power contraction will be expanded automatically.
|