Protection of PV System (industrial solar park)

Surge protectors designed to withstand high temperature and high voltage for photovoltaic (PV) systems.
Protection of PV System (industrial solar park)

DC Power Supply Line

  • Surge Protector for Photovoltaic System (600 V DC line use)
    MATP class II
    Model: MATP
    • Surge protection for photovoltaic array and power conditioner
    • Degraded head element is automatically separated from the power lines by the incorporated thermal breaker, and the LED lamp (turns off) and the relay contact alerts the failure status
    • Breakdown of the surge protector remotely detected with the alarm output
    • IP20 protection
    • IEC 61643-1 Class II
    • Maximum continuous operating voltage (Uc): 600 V DC
    • Discharge voltage (Line to earth): 600 V DC
    • Voltage protection level (Up): 2.5 kV
    • Maximum discharge current (Imax): 20 kA (MATP-600M), 40 kA (MATP-600H) (8/20 μs)
    • Operating temperature range -25 to +80°C (-13 to +176°F)
  • Surge Protector for Photovoltaic System (750 V DC, 1000 V DC line use)
    MATPH CEclass II
    Model: MATPH
    • Surge protection for photovoltaic array and power conditioner
    • Degraded head element is automatically separated from the power lines by the incorporated thermal breaker, and the LED lamp (turns off) and the relay contact alerts the failure status
    • Breakdown of the surge protector remotely detected with the alarm output
    • Photovoltaic system's resistance to earth is measurable without removing the SPD due to spark gap employed between line and earth
    • IP20 protection
    • IEC 61643-1 Class II
    • Maximum continuous operating voltage (Uc): 750 V DC (MATPH-750), 1000 V DC (MATPH-1000)
    • Discharge voltage (Line to earth): 500 V DC
    • Voltage protection level (Up): 2.5 kV (MATPH-750), 3.3 kV (MATPH-1000)
    • Maximum discharge current (Imax): 20 kA (8/20 μs)
    • Operating temperature range -25 to +80°C (-13 to +176°F)

Small Capacity Power Supply Line

  • Surge Protector for AC/DC Power Supply Use (photovoltaic system, instrument shelter)
    MDP-100T / MDP-200T class III
    Model: MDP-100T
    Model: MDP-200T
    • Designed for AC and specifically for DC power supplies up to 1 A
    • Beneficial for protecting instruments from counter electromotive force by inductors and of course normal lightning surges entering from power supply lines
    • 1 A fuse incorporated in element circuit
    • IEC 61643-1 Class III
    • Maximum line voltage (Uc): 120 V AC (peak voltage 170 V) (MDP-100T), 250 V AC (peak voltage 355 V) (MDP-200T)
    • Voltage protection level (Up): 400 V (MDP-100T), 800 V (MDP-200T)
    • Maximum discharge current (Imax): 1000 A (8/20 μs)
    • Operating temperature range -20 to +80°C (-4 to +176°F)

Standard Signal Line

  • Lightning Surge Protector for Standard Signal Line & Pulse Use (photovoltaic system, instrument shelter)
    MDP-24T / MDP-65T CE
    Model: MDP-24T
    Model: MDP-65T
    • Designed specifically for 4-20mA DC and pulse signal line including both 4-wire and 2-wire transmitters
    • Absorbs surges only without affecting instrumentation signal
    • No interruption of signal by unplugging surge protector element
    • Maximum continuous operating voltage (Uc): 30 V (MDP-24T), 70 V (MDP-65T)
    • Voltage protection level (Up): 45 V (MDP-24T), 110 V (MDP-65T)
    • Maximum discharge current (Imax): 5000 A (8/20 μs)
    • Operating temperature range -20 to +80°C (-4 to +176°F)
  • Lightning Surge Protector for Standard Signal Line & Pulse Use (life monitor, 24 V, 48 V or 65 V DC line voltage, photovoltaic system, instrument shelter)
    MDM2AT CE
    Model: MDM2AT
    • Designed specifically for 4-20 mA DC and pulse signal lines
    • Absorbs surges only without affecting instrumentation signal
    • Life monitor function helps you to decide when you should replace the surge protector; reduces time and effort for maintenance and prevents downtime
    • LED light and alarm output indicate the degradation and life span of the surge protection circuits
    • Maximum continuous operating voltage (Uc) Line to line: 30 V (24 V DC use), 70 V (48 V or 65 V DC use)
    • Voltage protection level (Up) Line to line: 45 V max. (24 V DC use), 100 V max. (48 V or 65 V DC use)
    • Discharge current capacity: 5000 A (8/20 μs)
    • Operating temperature range -20 to +70°C (-4 to +158°F)