Multi Power Monitoring / Logging Unit R9 Series
- Basic unit can measure up to 8 heavy current circuits on a common voltage input.
- Single-phase/2-wire and 3-wire, and three-phase/3-wire system use
- Easy setup with clamp-on current sensors for input
- Flexible range of 5 to 600 A input
- Time-stamped data logging in SD card
- Extension unit for eight additional current circuits or 8 discrete I/O can be attached.
Depending on the model.
-
Products Line up
Choose model No. to view data sheets.
Model No. Network Function R9MWTU Modbus RTU R9EWTU Modbus TCP (Ethernet) R9CWTU CC-Link R9LWTU LONWORKS -
Multi-channel Power Monitoring
The R9 Series Power Monitoring Unit is a compact all-in-one module that can measure up to 8 heavy current circuits with a common voltage input. An extension unit for additional 8 circuits (Model: R9WTU-EP) can be attached to the side of basic unit. At the maximum of 16 measuring input unit provides for cost-effective multi-channel power monitoring solution for office buildings and manufacturing plants.
A discrete I/O extension unit (Model: R9WTU-ED) is also available for 8 pulse inputs and 8 contact outputs. Pulse count signals such as gas/air pressure and water flow from other utility equipment, and production unit count signals can be taken in all together to the R9 unit for use with energy consumption rate calculation and energy efficiency improvement analysis of an entire manufacturing line.
-
Clamp-on Current Sensor Input
Current sensors that can take in a flexible range of 5 to 600 amperes directly to the unit can be fitted easily without need of extensive installation work. They are purchased independently to minimize introduction cost of the energy monitoring system that can be expanded later when more measuring points are needed.
Model: CLSE
-
Offline Monitoring
The unit is equipped with a SD memory card slot. Data stored in its internal memory are transferred to the card at 0 minute every hour. A 4-GB SD memory can store information of 8 channels for approximately 16 years.
Energy (watthour) and pulse count input data per hour for each channel are stored with date/time. Voltage, current and power in addition to energy and pulse count per minute are also stored. All data are exported to the SD memory card every hour and saved in a CSV format file.
-
Online Monitoring
Modbus RTU, Modbus TCP (Ethernet), CC-Link or LONWORKS interface types are available as standard. All parameters can be polled from a SCADA system on the PC: current, voltage, active/reactive/apparent power, power factor, frequency, active/reactive/apparent energy, harmonic distortion and date/time.
Contact outputs at the discrete extension I/O unit can be controlled from the host via the network for alarm and external count purposes.
-
Specifications
Configuration Single-phase/2-wire and 3-wire, three-phase/3-wire Voltage input Delta voltage: 400V AC (line to line)
Phase voltage: 230V AC (line to neutral)
Selectable primary range: 50 to 400000VCurrent input Clamp-on current sensor model CLSE: 5A, 50A, 100A, 200A, 400A and 600A
Selectable primary range: 1 to 20000AAuxiliary power supply 100-240V AC or 110-240V DC Operating temperature -10 to +55°C (14 to 131°F) Operating humidity 30 to 90% RH (non-condensing) Mounting Surface or DIN rail Accuracy
(except current
sensor accuracy)Voltage, current, power: ±0.5% of rating
Energy: ±1%
Power factor: ±1.5%
Frequency: ±0.1% of rating
Harmonic contents: ±2% of ratingSampling time Harmonic contents & frequency: 1 sec. or less
Other: 500 msec. or lessInsulation resistance 100 MΩ or more with 500V DC Dielectric strength 1500V AC @1 minute Dimensions Basic unit: 125x122x80 mm (4.92”x4.80”x3.15”)
Extension unit: 93x122x80 mm (3.66”x4.80”x3.15”) when attached to the basic unit
(DIN rail mount)Recommended
SD cardHagiwara Sys-Com NSDA-004GT
Apacer Technology AP-ISD04GIS4B-T
Component Identification (Model: R9EWTU)
Application Example